[Zurück]


Zeitschriftenartikel:

T. Zseby, J. Fabini, D. Rani:
"Synchrophasor Communication";
E&I Elektrotechnik und Informationstechnik (eingeladen), 131 (2014), 1; S. 8 - 13.



Kurzfassung deutsch:
Synchronized phasor measurements provide the basis for fine-grained wide area power quality monitoring in electric grids. Time-synchronized phasor measurement units (PMUs) are deployed at different locations in the grid and report 10-60 measurements/second to energy management systems or other applications. For control applications it is crucial to receive measurement data as soon as possible after a state change in order to trigger corrective actions in time to prevent incidents in the grid.
In this paper we analyze characteristics of synchrophasor M2M communication for different network technologies, including VDSL, HSPA and LTE networks. We briefly review synchrophasor communication approaches and real-time demands. We then emulate PMU traffic and perform measurements on different networks. We show how the underlying technology influences one-way delay patterns for synchrophasor communication, which has direct implication on the achievable real-time properties.

Kurzfassung englisch:
Synchronized phasor measurements provide the basis for fine-grained wide area power quality monitoring in electric grids. Time-synchronized phasor measurement units (PMUs) are deployed at different locations in the grid and report 10-60 measurements/second to energy management systems or other applications. For control applications it is crucial to receive measurement data as soon as possible after a state change in order to trigger corrective actions in time to prevent incidents in the grid.
In this paper we analyze characteristics of synchrophasor M2M communication for different network technologies, including VDSL, HSPA and LTE networks. We briefly review synchrophasor communication approaches and real-time demands. We then emulate PMU traffic and perform measurements on different networks. We show how the underlying technology influences one-way delay patterns for synchrophasor communication, which has direct implication on the achievable real-time properties.

Schlagworte:
PMU, 3G, network measurements, phasor measurements, one-way delay, phasor measurement units, M2M communication, Phasor Messungen, Verzögerungszeiten, Phasor Measurement Units, M2M Kommunikation


"Offizielle" elektronische Version der Publikation (entsprechend ihrem Digital Object Identifier - DOI)
http://dx.doi.org/10.1007/s00502-013-0193-6


Erstellt aus der Publikationsdatenbank der Technischen Universität Wien.