Vorträge und Posterpräsentationen (mit Tagungsband-Eintrag):
K. Eder, H. Konder, T. Bednar:
"Effect of different façade systems on the cooling capacity of a cooled ceiling - Tracer gas measurement of the air flow";
Vortrag: 10th Nordic Symposium on Building Physics,
Lund, Sweden;
15.06.2014
- 19.06.2014; in: "NSB 2014,10th Nordic Symposium on Building Physics",
Grafisk gruppen AB,
(2014),
ISBN: 978-91-88722-53-9;
Paper-Nr. 5,
8 S.
Kurzfassung englisch:
The aim of the work is to clarify how the façade system and the cooling ceiling impacts the air movement within a room. Therefore tracer gas measurements with different inject locations and different room set-ups were done. One part of the results show the impact of different façade systems - a single skin façade and a single
storey double skin façade - on the air movement. The measurements show an increase of concentration within the ceiling zone which is attributed to a higher air flow rate over the ceiling.
Furthermore different set ups of the cooling ceilings were measured - one with natural ventilation over the suspended cooling ceiling and one without natural ventilation. The measurement results
show that there is a decrease of concentration due to missing natural ventilation. The measurement results show a clear difference in the rate of concentration on different room points due to solar radiation, the location of impact and the room set up.
Schlagworte:
Air flow, tracer gas measurement, comfort, façade systems, cooling ceiling, cooling capacity
Erstellt aus der Publikationsdatenbank der Technischen Universität Wien.